GE GFK-0787B Noise Reduction Machine User Manual


 
5
5-19GFK-0787B Chapter 5 Diagnostics
Code MeaningMessage
10146 Config mismatch A/B/C All three PLCs mismatch
10147 Config changed A PLC A config changed
10148 Config changed B PLC B config changed
2 Config changed C PLC C config changed
10201 Unauthorized GMR Access Inter-PLC Comms module was invoked with incorrect password
10202 Incorrect GMR Version Inter-PLC Comms module has incorrect GMR version number
10203 GMR Software Exception Inter-PLC Comms module was called with invalid call number
10204 Invalid GMR Pointer Inter-PLC Comms module was called with invalid data pointer
10211 Comms Fail PLC A bus a Communications with PLC A has failed on bus a
10212 Comms Fail PLC B bus a Communications with PLC B has failed on bus a
10213 Comms Fail PLC C bus a Communications with PLC C has failed on bus a
10221 Comms Fail PLC A bus b Communications with PLC A has failed on bus b
10222 Comms Fail PLC B bus b Communications with PLC B has failed on bus b
10223 Comms Fail PLC C bus b Communications with PLC C has failed on bus b
10241 Big err rate, PLC A on a PLC detected a high data CRC failure rate communicating with PLC A on bus a
10242 Big err rate, PLC A on b PLC detected a high data CRC failure rate communicating with PLC A on bus b
10243 Big err rate, PLC B on a PLC detected a high data CRC failure rate communicating with PLC B on bus a
10244 Big err rate, PLC B on b PLC detected a high data CRC failure rate communicating with PLC B on bus b
10245 Big err rate, PLC C on a PLC detected a high data CRC failure rate communicating with PLC C on bus a
10246 Big err rate, PLC C on b PLC detected a high data CRC failure rate communicating with PLC C on bus b
10251 Invalid Switch Case GMR2 software detected an illegal internal condition
10301 Unauthorized GMR access Fault Processor Module was invoked with incorrect password
10302 Incorrect version number Fault Processor Module was invoked with incorrect version number
10303 Invalid call number Call number was invalid
10305 Invalid GMR Pointer The supplied diagnostics pointer is out of range for the required memory type
10306 Invalid Block Size Incorrect block size was specified
10307 Invalid Digital Address Incorrect address of digital I/O was specified
10308 Invalid Analog Address Incorrect address of analog I/O was specified
10310 Invalid block type Block type currently unsupported
10311 GMR3 Rr Ss comreq Fail A COMREQ sent by GMR to a bus controller in rack r slot s has failed
10312 GMR S/W Except. %L %L range error
10313 Value out of range Calculated value is out of range
10322 IO Reset Seq Timeout I/O reset timed out in step 2
10323 IO Reset Seq Timeout I/O reset timed out in step 4
10324 IO Reset Seq Timeout I/O reset timed out in step 6
10328 IO Reset Seq Timeout I/O reset timed out in step 8
10330 IO Reset Seq Timeout I/O reset timed out in step 10
10601 Unauthorized GMR Access I/O Module was invoked with the incorrect password
10602 Invalid GMR Version I/O Module S/W version does not match expected version
10603 GMR S/W Except. Call I/O Module was invoked with incorrect call number
10604 GMR S/W Except, %L I/O Module was invoked with out of range input parameters
10607 Invalid Switch Case No cases satisfied by switch condition
10801 Unauthorized GMR Access GMR Configuration Module was invoked with incorrect password
10802 GMR S/W Except Null FH GMR Configuration Module failed to load fault handler
10802 GMR S/W Except I/O FH GMR Configuration Module encountered an error loading the fault handler
10803 GMR S/W Except call no GMR Configuration Module detected call number exception
10804 ADL rack r slot s flt GMR Configuration Module failed to build active device list
10805 GMR S/W Except %L GMR Configuration Module detected invalid diagnostic or error references
10806 GMR Invalid switch GMR Configuration Module detected invalid switch case
10810 GMR config util invalid GMR Config Module detected incompatibility with configuration utility
10811 GMR cfg err GBCxx GMR Configuration Module detected invalid GBC record xx in the config data
10812 GMR cfg err GBCxx I/O yy GMR Configuration Module detected invalid GBC record yy in GBC record xx of the
config data
10813 GMR cfg err CPU type GMR Configuration Module detected incompatible CPU type in the config data