5-22 Genius Modular Redundancy Flexible Triple Modular Redundant (TMR) System
User’s Manual –March 1995
GFK-0787B
Code MeaningMessage
11453 GMR12–tmplt too small GMR14 has detected an internal error condition
11455 GMR15–IS x at y GMR15 statemachine went to step x (illegal). Step no. at offset y in GMR15 diagnos-
tics
11456 GMR15–ST x at y GMR15 state mach. exceeded allowed time in step x. Step no. at offset y in GMR15 diag-
nostics
11457 GMR15–IW x GMR15 has output an illegal waycode of x
11458 GMR15–tmplt too small GMR14 has detected an internal error condition
11501 Unauthorized GMR Access GMR15 was invoked with incorrect password
11502 Incorrect GMR Version GMR15 version number does not match the GMR system version number
11503 GMR Software Exception An invalid call number was detected
11504 Invalid GMR Pointer The error code pointer was out of bounds
11505 More than 1 Master GMR15 detected that more than 1 PLC was operating as master
11506 Invalid Switch Case GMR detected an illegal internal condition
11507 Discrep NAK PLC A PLC A failed to acknowledge discrepancy results
11508 Discrep NAK PLC B PLC B failed to acknowledge discrepancy results
11509 Discrep NAK PLC C PLC C failed to acknowledge discrepancy results
11510 Disc results read fault The PLC was unable to read output discrepancy results data from the master PLC
11511 DQ x.y.1.z –> d/f/s The PLC expected to dequeue an input autotest results datagram from the device at
rack x, slot y, SBA (serial bus address) z. Instead, an invalid datagram was dequeued
with function code f and subfunction code s from SBA (bus address) d
11511 CQ x.y.1.z –> d/f/s The PLC expected no datagram to be in the queue for the device at rack x, slot y, seri-
al bus address z. Instead, an invalid datagram was found with function code f, and
subfunction code s, from serial bus address d
11513 Xtalk results read flt Non-master could not read input autotest results from master PLC
11521 CR fail x.y.l.z f/s COMREQ with function code f and subfunction code s failed when sent to the device
at rack x, slot y, SBA z
11522 Trans x.y.l.z cccccccc Output discrepancy processing could not be completed for the channels marked in c
on the device at rack x, slot y, SBA z,due to transitioning outputs
11523 Null timeout from PLC A Timeout occurred while waiting for PLC A to transmit a null test number
11524 Null timeout from PLC B Timeout occurred while waiting for PLC B to transmit a null test number
11525 Null timeout from PLC C Timeout occurred while waiting for PLC C to transmit a null test number
11530 I/O S/D r.s.b.d I/O Shutdown on the specified block
11530 I/O S/D cancel r.s.b.d I/O Shutdown cancelled on the specified block
11530 I/O S/D 8hrs r.s.b.d I/O Shutdown in 8 hours on the specified block
11530 I/O S/D 1hr r.s.b.d I/O Shutdown in 1 hour on the specified block
1rsdd I/P A/T res timeout A/T results for SBA dd on GBC at rack r slot s