Accel/Decel
Standard acceleration and deceleration is
linear. The inverter CPU can also
calculate an S-curve acceleration or
deceleration curve as shown. This profile
is useful for favoring the load
characteristics in particular applications.
Curve settings for acceleration and
deceleration are independently selected.
To enable the S-curve, use function A097
(acceleration) and A098 (deceleration).
“A” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Acceleration curve selectionA097
ACC LINE L
Set the characteristic curve of
Acc1 and Acc2, two options:
00…linear
01…S-curve
U
00 00
−
Deceleration curve selectionA098
DEC LINE L
Set the characteristic curve of
Dec1 and Dec2, two options:
00…linear
01…S-curve
U
00 00
−
A097 = 00
A
ccel. curve selection
Output
frequency
S-curve
Linear
t
0
A097 = 01
Target
freq.
Acceleration period
3
−
27
Configuring Drive