The following table lists the holding registers for the “B” Group Fine Tuning Functions.
List of Holding Registers
Network Data
Func.
Code
Name R/W Description
Reg. Range Res.
B001 Selection of automatic
restart mode
R/W Select inverter restart method,
Four option codes:
00…Alarm output after trip, no
automatic restart
01…Restart at 0Hz
02…Resume operation after
frequency matching
03…Resume previous freq. after
freq. matching, then
decelerate to stop and
display trip info
10A5h 0, 1, 2, 3
−
B002 Allowable under-
voltage power failure
time
R/W The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to 25
sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.
10A6h 3 to 250 0.1 sec
B003 Retry wait time before
motor restart
R/W Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
10A7h 3 to 1000 0.1 sec
B004 Instantaneous power
failure / under-voltage
trip alarm enable
R/W Two option codes:
00…Disable
01…Enable
10A8h 0, 1
−
B005 Number of restarts on
power failure / under-
voltage trip events
R/W Two option codes:
00…Restart 16 times
01…Always restart
10A9h 0, 1
−
B011 Start freq to be used in
case of freq pull-in
restart
R/W Three option codes:
00…freq at previous shutoff
01…start from max. Hz
02…start from set frequency
1170 0, 1, 2
−
B012 Level of electronic
thermal setting
R/W 10ADh
B212 Level of electronic
thermal setting, 2nd
motor
R/W
Set a level between 20% and
100% for the rated inverter
current.
1527h
2000 to
10000
0.01 %
B013 Electronic thermal
characteristic
R/W 10AEh
B213 Electronic thermal
characteristic, 2nd
motor
R/W
Select from three curves, option
codes: *1
00…Reduced torque 1
01…Constant torque
02… Reduced torque 2
1528h
0, 1, 2
−
B
−
31
Appendix B