Standard Functions
NOTE:. Mark “9” in B031=10 shows the accessible parameters when B031 is set “10”,
high level access.
“A” Group Parameters Default Setting
Func.
Code
Name
-FE
(EU)
-FU
(USA)
B031
=10
User
Setting
A001 Frequency source setting 01 00
U
A201 Frequency source setting, 2nd motor 01 00
U
A002 Run command source setting 01 02
U
A202 Run command source setting, 2nd motor 01 02
U
A003 Base frequency setting 50.0 60.0
U
A203 Base frequency setting, 2nd motor 50.0 60.0
U
A004 Maximum frequency setting 50.0 60.0
U
A204 Maximum frequency setting, 2nd motor 50.0 60.0
U
A005 [AT] selection 02 02
9
A011 Pot./O-L input active range start
frequency
0.0 0.0
9
A012 Pot./O-L input active range end
frequency
0.0 0.0
9
A013 Pot./O-L input active range start voltage 0. 0.
9
A014 Pot./O-L input active range end voltage 100. 100.
9
A015 Pot./O-L input start frequency enable 01 01
9
A016 External frequency filter time constant 8. 8.
9
A020 Multi-speed 0 setting 0.0 0.0
9
A220 Multi-speed 0 setting, 2nd motor 0.0 0.0
9
A021 Multi-speed 1 setting 0.0 0.0
9
A022 Multi-speed 2 setting 0.0 0.0
9
A023 Multi-speed 3 setting 0.0 0.0
9
A024 Multi-speed 4 setting 0.0 0.0
9
A025 Multi-speed 5 setting 0.0 0.0
9
A026 Multi-speed 6 setting 0.0 0.0
9
A027 Multi-speed 7 setting 0.0 0.0
9
A028 Multi-speed 8 setting 0.0 0.0
9
A029 Multi-speed 9 setting 0.0 0.0
9
A030 Multi-speed 10 setting 0.0 0.0
9
A031 Multi-speed 11 setting 0.0 0.0
9
A032 Multi-speed 12 setting 0.0 0.0
9
A033 Multi-speed 13 setting 0.0 0.0
9
A034 Multi-speed 14 setting 0.0 0.0
9
A035 Multi-speed 15 setting 0.0 0.0
9
A038 Jog frequency setting 1.00 1.00
9
A039 Jog stop mode 00 00
9
A041 Torque boost select 00 00
U
A241 Torque boost select, 2
nd
motor 00 00
U
A042 Manual torque boost value 1.8 1.8
9
A242 Manual torque boost value, 2
nd
motor 0.0 0.0
9
C
−
3
Appendix C