Hitachi X200 Series Power Supply User Manual


 
C102 Reset selection Determines response to Reset input
[RS].
Three option codes:
00Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02Cancel trip state at input ON
transition, no effect if in Run Mode
114Ah 0, 1, 2
C141 Input A select for logic
output
R/W 1150h
C142 Input B select for logic
output
R/W
See “Output Logic and Timing” on
page 3–63
1151h
0, 1, 2, 3,
4, 5, 6, 7,
8, 10, 43
C143 Logic function select R/W Applies a logic function to calculate
[LOG] output state, Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
1152h 0, 1, 2
B38