Hitachi X200 Series Power Supply User Manual


 
“B” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Selection of automatic restart
mode
B001
IPS POWR ALM
Select inverter restart method,
Four option codes:
00Alarm output after trip, no
automatic restart
01Restart at 0Hz
02Resume operation after
frequency pull-in
03Resume previous freq. after
freq. pull-in, then decelerate
to stop and display trip info
U
00 00
Allowable under-voltage
power failure time
B002
IPS Time 0001.0s
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to 25
sec. If under-voltage exists longer
than this time, the inverter trips,
even if the restart mode is
selected.
U
1.0 1.0 sec.
Retry wait time before motor
restart
B003
IPS Wait 0001.0s
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0 1.0 sec.
Instantaneous power failure /
under-voltage trip alarm
enable
B004
IPS TRIP OFF
Two option codes:
00Disable
01Enable
U
00 00
Number of restarts on power
failure / under-voltage trip
events
B005
IPS RETRY 16
Two option codes:
00Restart 16 times
01Always restart
U
00 00
Start freq to be used in case
of freq pull-in restart
B011
FSch Md CUTOFF
Three option codes:
00freq at previous shutoff
01start from max. Hz
02start from set frequency
U
00 00
Deceleration rate of freq pull-
in restart setting
B029
FSch CNS 0000.5s
Sets the deceleration rate when
frequency pull-in restart, range is
0.1 to 3000.0, resolution 0.1
U
0.5 0.5 sec.
Current level of frequency
pull-in restart setting
B030
FSch LVL 002.60A
Sets the current level of
frequency pull-in restart, range is
0.2*inverter rated current to
2.0*inverter rated current,
resolution 0.1
U
Rated
current
A
3
33
Configuring Drive
Parameters