Symptom/condition Probable Cause Solution
If using the analog input, is the
current or voltage at [O] or [OI]?
Check the wiring.
Check the potentiometer or
signal generating device.
Is the load too heavy? Reduce the load.
Heavy loads activate the
overload restriction feature
(reduces output as needed).
The motor speed will not
reach the target frequency
(desired speed).
Is the inverter internally limiting
the output frequency?
Check max frequency setting
(A004)
Check frequency upper limit
setting (A061)
The rotation is unstable
Is the load fluctuation too great?
Is the supply voltage unstable?
Is the problem occurring at a
particular frequency?
Increase the motor capacity
(both inverter and motor).
Fix power supply problem.
Change the output frequency
slightly, or use the jump
frequency setting to skip the
problem frequency.
The RPM of the motor does
not match the inverter
output frequency setting.
Is the maximum frequency setting
A004 correct?
Does the monitor function D001
display the expected output
frequency?
Verify the V/f settings match
motor specifications.
Make sure all scaling (such as
A011 to A014) is properly set.
Was power turned OFF after a
parameter edit but before pressing
the Store key?
Edit the data and press the
Store key once.
No download has
occurred
Edits to data are permanently
stored at power down. Was the time
from power OFF to power ON less
than six seconds?
Wait six seconds or more
before turning power OFF
after editing data.
Inverter
data us not
correct
The download
to the inverter
was attempted
Was the power turned OFF within
six seconds after the display
changed from REMT to INV?
Copy the data to the inverter
again, and keep power ON for
six seconds or more after
copying.
True for
certain
parameters
Is the inverter in Run Mode? Some
parameters cannot be edited during
Run Mode.
Put inverter in Stop Mode
(press the Stop/reset key).
Then edit the parameter.
A
parameter
will not
change
after an
edit
(reverts to
old
setting).
True for all
parameters
If you’re using the [SFT] intelligent
input (software lock function)—is
the [SFT] input ON?
Change the state of the SFT
input, and check the B031
parameter (SFT mode).
64
Troubleshooting and