Hitachi X200 Series Power Supply User Manual


 
X200 Inverter Specifications, continued…
Item 200V class Specifications
EU version 015SFEF 022SFEF X200 inverters,
200V models
USA version 015NFU 022NFU 037LFU
kW 1.5 2.2 3.7Applicable motor size *2
HP 2 3 5
230V 2.8 3.9 6.3Rated capacity
(kVA)
240V 2.9 4.1 6.6
Rated input voltage - SFEF type: 1-phase input only
- NFU type: 1-phase or 3-phase input
- LFU type: 3-phase input only
1-phase: 200V-15% to 240V +10%, 50/60Hz ±5%
3-phase: 200V-15% to 240V ±10%, 50/60Hz ±5%
EU version SFE series : EN61800-3 category C1 filterIntegrated EMC
filter
USA version
EU version 16.0 22.5 Rated input
current (A)
USA version 9.3 13.0 20.0
Rated output voltage *3 3-phase: 200 to 240V (proportional to input voltage)
Rated output current (A) 7.1 10.0 15.9
Starting torque *7 100% at 6Hz
50%:
60Hz 20%:
60Hz
Dynamic braking,
approx. % torque
(short time stop
from 50/60Hz) *8
Capacitive feedback type, dynamic braking unit and
braking resistor optional, individually installed
Braking
DC braking Variable operating frequency, time, and braking force
Kg 2.4 2.5 EU version
(-SFE)
lb 5.30 5.52
Kg 2.3 2.4 2.3
Weight
USA version
(-NFU)
lb 5.08 5.30 5.08
1
7
Getting started