Hitachi X200 Series Power Supply User Manual


 
Output Logic and Timing
Logic Output Function – The inverter has a built-in logic output feature. You can select
any two of the other nine intelligent output options for internal inputs. Then, configure
the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as
desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021,
or C026 to route the logical result to terminal [11] or the relay terminals.
The following table shows all four possible input combinations with each of the three
available logic operations.
Input Status [LOG] Output State
A B AND OR XOR
000 00
010 11
100 11
111 10
“C” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Input A select for logic
output
C141
LogicOut1 RUN
U
00 00
Input B select for logic
output
C142
LogicOut2 FA1
11 programmable functions
available for logic (discrete)
outputs
00RUN 01FA1 02FA2
03OL 04OD 05AL
06Dc 07FBV 08NDc
09LOG 10ODc 43LOC
U
01 01
Logic function selectC143
LogicOPE AND
Applies a logic function to calculate
[LOG] output state,
Three options:
00[LOG] = A AND B
01[LOG] = A OR B
02[LOG] = A XOR B
U
00 00
Intelligent outputs
used as internal
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
Input A
C141
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
Input B
C142
Logic function
AND, OR, XOR
C021
11
AL1
AL0
AL2
C026
3
63
Configuring Drive
Parameters