Network Communications Settings
The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
“ModBus Network Communications” on page B-1 for more information on controlling
any monitoring your inverter from a network.
“C” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Selection of OPE / ModBusC070
PARAM REM
Two option codes:
02…OPE or option
03…ModBus (485)
U
02 02
−
Communication speed
selection
C071
COM BAU 4800
Three option codes:
04…4800 bps
05…9600 bps
06…19200 bps
U
06 04 baud
Node allocationC072
COM ADR 00001
Set the address of the inverter on
the network. Range is 1 to 32
U
1. 1.
−
Communication parity
selection
C074
COM PRTY NON
Three option codes:
00…No parity
01…Even parity
02…Odd parity
U
00 00
−
Communication stop bit
selection
C075
COM STP 1BIT
Range is 1 to 2
U
11bit
Communication error selectC076
COM ESlct None
Selects inverter response to
communications error.
Five options:
00…Trip (Error code E60)
01…Decelerate to a stop and trip
(Error code E60)
02…Disable
03…Free run stop (coasting)
04…Decelerate to a stop
U
02 02
−
Communication error time-
out
C077
COM ETIM 000.00s
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
U
0.00 0.00 sec.
Communication wait timeC078
COM Wait 00000ms
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0. 0. msec.
3−60
Configuring Drive
Parameters