Hitachi X200 Series Power Supply User Manual


 
Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run
command via the terminal [RV], the inverter executes the Reverse Run command (high)
or Stop command (low).
Option
Code
Terminal
Symbol
Function Name State Description
ON Inverter is in Run Mode, motor runs forward00 FW Forward Run/Stop
OFF Inverter is in Stop Mode, motor stops
ON Inverter is in Run Mode, motor runs reverse01 RV Reverse Run/Stop
OFF Inverter is in Stop Mode, motor stops
Valid for inputs: C001~C005
Required settings A002 = 01
Notes:
When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
When a terminal associated with either [FW]
or [RV] function is configured for
normally
closed
, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.
Example (default input configuration shown
– see page 3-49)
See I/O specs on page 4-6.
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single
Run key issues a Run FWD command or Run REV command. However, it has no effect
on the [FW] and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the
motor starts rotation and is dangerous! Before turning power ON, confirm that the Run
command is not active.
5 4 3 2 1 L
PLC
P24
FWRV
4
11
Operations and
Monitoring