Hitachi X200 Series Power Supply User Manual


 
“D” Group: Monitoring Functions
You can access important parameter values with the “D” Group monitoring functions,
whether the inverter is in Run Mode or Stop Mode. After selecting the function code
number for the parameter you want to monitor, press the Function key once to show the
value on the display. In function D005 and D006, the intelligent terminal use individual
segments of the display to show ON/OFF status.
If the inverter display is set to monitor a parameter and powerdown occurs, the inverter
stores the present monitor function setting. For your convenience, the display
automatically returns to the previously monitored parameter upon the next powerup.
“D” Function
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
Units
Output frequency monitorD001
FM 000.00Hz
Real time display of output
frequency to motor from
0.0 to 400.0Hz
Hz
Output current monitorD002
Iout 0000.0A
Filtered display of output current to
motor (100 ms internal filter time
constant), range is
0 to 999.9 ampere
A
Rotation direction monitorD003
Dir STOP
Three different indications:
“F” Forward
“o” Stop
“r” Reverse
−−
Process variable (PV),
PID feedback monitor
D004
FB 00000.00%
Displays the scaled PID process
variable (feedback) value (A075 is
scale factor),
0.00 to 99.99, 100.0 to 999.9
1000. to 9999., 1000 to 999,
and 10000 to 99900
% times
constant
Intelligent input
terminal status
D005
IN-TM LHLHL
Displays the state of the intelligent
input terminals:
−−
Intelligent output
terminal status
D006
OUT-TM L H
Displays the state of the intelligent
input terminals:
−−
ON
OFF
54
3
21
Terminal numbers
Terminal numbers
AL
11
ON
OFF
36
Configuring Drive
Parameters