Hitachi X200 Series Power Supply User Manual


 
Second Acceleration and Deceleration Functions
The X200 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (F002) or deceleration (F003) changes to the second
acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to
trigger this transition. These profile options are also available for the second motor
settings. Select a transition method via A094 as depicted below. Be careful not to
confuse the
second acceleration/deceleration settings
with settings for the
second motor
!
“A” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Acceleration (2) time settingA092
ACC 2 0015.00s
Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
9
15.00 15.00 sec
Acceleration (2) time setting,
2nd motor
A292
2ACC2 0015.00s
Duration of 2nd segment of
acceleration, 2nd motor, range is:
0.01 to 3000 sec.
9
15.00 15.00 sec
Deceleration (2) time settingA093
DEC 2 0015.00s
Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
9
15.00 15.00 sec
Deceleration (2) time setting,
2nd motor
A293
2DEC2 0015.00s
Duration of 2nd segment of
deceleration, 2nd motor, range is:
0.01 to 3000 sec.
9
15.00 15.00 sec
Select method to switch to
Acc2/Dec2 profile
A094
ACC CHG TM
Two options for switching from
1st to 2nd accel/decel:
002CH input from terminal
01Transition frequency
U
00 00
Select method to switch to
Acc2/Dec2 profile, 2nd motor
A294
2ACCCHG TM
Two options for switching from
1st to 2nd accel/decel:
002CH input from terminal
01Transition frequency
(2nd motor)
U
00 00
A094 = 00
Transition via 2CH input
Output
frequency
A
ccel 1
A
ccel 2
2CH
input
1
0
t
t
0
A094 = 01
Transition via freq. level
Output
frequency
A
ccel 1
A
ccel 2
t
0
A095
Frequency
transition point
3
25
Configuring Drive
Parameters