Hitachi X200 Series Power Supply User Manual


 
Option
Code
Terminal
Symbol
Function Name State Description
ON
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)
07 FBV Feedback Value
Check
OFF
Transitions to OFF when the PID Feedback
Value (PV) exceeds the PID High Limit (C052)
Transitions to OFF when the inverter goes from
Run Mode to Stop Mode
Valid for inputs: 11, AL0 – AL2
Required settings
A076, C052, C053
Notes:
The [FBV] is designed for implementing two-
stage control. The PV high limit and PV low
limit parameters, C052 and C053, do not
function as process alarm thresholds. Terminal
[FBV] does not provide a PID alarm function.
The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negativegoing turn-off spike generated by the
coil from damaging the inverter’s output
transistor.
Example for terminal [11] (default output
configuration shown – see page 3-54):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see page 4-35 and 3-54):
See I/O specs on page 4-6
RY
Inverter output
terminal circuit
CM2 11
FBV
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
FBV
4
47