Hitachi X200 Series Power Supply User Manual


 
Force Operation from Digital Operator
This function permits a digital operator interface to override the following two settings
in the inverter:
A001 - Frequency source setting
A002 - Run command source setting
When using the [OPE] terminal input, typically A001 and A002 are configured for
sources other than the digital operator interface for the output frequency and Run
command sources, respectively. When the [OPE] input is ON, then user has immediate
command of the inverter, to start or stop the motor and to set the speed.
Option
Code
Terminal
Symbol
Function Name State Description
ON Forces the operator interface to override:
A001 - Frequency Source Setting, and A002 - Run
Command Source Setting
31 OPE Force Operation
from Digital
Operator
OFF Parameters A001 and A002 are in effect again,
for the frequency source and the Run command
source, respectively
Valid for inputs: C001~C005
Required settings
A001 (set not equal to 00)
A002 (set not equal to 02)
Notes:
When changing the [OPE] state during Run
Mode (inverter is driving the motor), the
inverter will stop the motor before the new
[OPE] state takes effect.
If the [OPE] input turns ON and the digital
operator gives a Run command while the
inverter is already running, the inverter stops
the motor. Then the digital operator can control
the motor.
Example (default input configuration shown—see
page 3–49):
See I/O specs on page 4–6.