Hitachi X200 Series Power Supply User Manual


 
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in
the tables below.
Motor Output Torque
Input
Voltage
kW HP
Inverter Model
Power Terminal
Wiring Size
Range (AWG)
Ft-lbs (N-m)
0.2 1/4 X200-002SFE/NFU
0.4 1/2 X200-004SFE/NFU
0.6 0.8
0.55 3/4 X200-005SFE
0.75 1 X200-007SFE/NFU
14
(75C only)
1.1 1 1/2 X200-011SFE
1.5 2 X200-015SFE/NFU
12
2.2 3 X200-022SFE/NFU 10
0.9 1.2
3.7 5 X200-037LFU 12 0.9 1.2
200V
Class
0.4 1/2 X200-004HFE/HFU
0.75 1 X200-007HFE/HFU
1.5 2 X200-015HFE/HFU
16
2.2 3 X200-022HFE/HFU
3.0 4 X200-030HFE
4.0 5 X200-040HFE/HFU
14
(60C only)
0.9 1.2
400V
Class
Torque
Terminal Connector
Wiring Size
Range (AWG)
Ft-lbs (N-m)
Logic and Analog connectors 30 – 16 0.16 – 0.19 0.22 – 0.25
Relay connector 30 – 14 0.37 – 0.44 0.5 – 0.6
Wire Connectors
WARNING: Field wiring connections must be made by a UL Listed and CSA certified
ring lug terminal connector sized for the wire gauge being used. The connector must be
fixed using the crimping tool specified by the connector manufacturer.
Terminal (ring lug)
Cable support
Cable
xiv