B089: Monitor display select for networked inverter – When the X200 inverter is
controlled via network, the inverter’s keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 sill be displayed on the keypad. See
“Local Monitoring During Network Operation” on page 3-8 for more details.
B092: Cooling Fan Control – You can select the performance of the cooling fan (if your
inverter has the fan) whether it stops or keep on running, after the inverter stops the
motor. This can result in an additional energy saving.
“B” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
M
ode
Edit
-FE
(EU)
-FU
(USA)
Units
Monitor display select for
networked inverter
B089
PANEL d001
Selects the parameter displayed on the
keypad display when the inverter is
networked, 7 options:
01Output frequency monitor
02Output current monitor
03Rotation direction monitor
04Process variable (PV), PID
feedback monitor
05Intelligent input terminal status
06Intelligent output terminal status
07Scaled output frequency monitor
9
01 01
Cooling fan controlB092
FAN-CTRL OFF
Selects when the fan is ON per inverter
operation, three options:
00Fan is always ON
01Fan is ON during run, OFF during
stop (5 min. delay from ON to
OFF
)
02Fan is temperature controlled
U
00 00
344