Add Frequency – The inverter can add or subtract on offset value to the output
frequency setting which is specified by A001 (will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter A145. the ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By
configuring an intelligent input as the [ADD] terminal, your application can selectively
apply the fixed value in A145 to offset (positively or negatively) the inverter output
frequency in real time.
“A” Function Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
ADD frequencyA145
ST-PNT 0000.0Hz
An offset value that is applied to
the output frequency when the
[ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
9
0.0 0.0 Hz
ADD direction selectA146
ADD DIR PLUS
Two options:
00…Plus (adds A145 value to the
output frequency setting)
01…Minus (subtracts A145 value
from the output frequency
setting)
U
00 00
−
Keypad potentiometer
Control terminal
Function F001 setting
ModBus network input
Calculate function output
Σ
+
A001
Frequency source setting
Output frequency setting
A145
A
DD frequenc
y
A146
A
DD direction select
+/-
Intelligent input
[ADD]
3−30
Configuring Drive
Parameters