H9 ASD Installation and Operation Manual 135
Retry Selection
Program Protection Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart
function:
Input Phase Loss (Input Phase Failure)
Output Phase Loss (Output Phase Failure)
Output Current Protection Fault
Output Current Detector error
Load side overcurrent at start
Earth Fault (Ground Fault)
Overcurrent During Acceleration
Arm Overcurrent at start-up
DBR Resistor Overcurrent
•Low Current
Voltage Drop In Main Circuit
EEPROM Data Fault (EEPROM Fault)
Flash Memory/Gate Array/RAM-ROM Fault
CPU Fault
Emergency Off (EMG)
Communication Error
Option Fault
Sink/Source Setting Error
Overspeed Error
Overtorque
•Key Error
External Thermal Error
Externally-controlled Interrupt
See the section titled System Setup Requirements on pg. 8 for more information
on this setting.
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
F303 F303