Toshiba H9 Network Card User Manual


 
210 H9 ASD Installation and Operation Manual
Communications Option (DeviceNet/Profibus) Setting 2
Program Communications Communication Settings
While using the DeviceNet/Profibus communications protocol, parameters
F831F836 allow the user to select the ASD memory location that holds the
Command/Frequency/Monitoring instructions to be applied to the ASD for
Communications Option Settings 27, respectively.
See the DeviceNet Option Instruction Manual (P/N 58683) for more
information on this parameter.
Settings:
0 — Disabled
1 — FA06 (ALCAN Command 1)
2 — FA23 (ALCAN Command 2)
3 — FA07 (ALCAN Frequency Command, 0.01 Hz)
4 — FA33 (Torque Command, 0.01%)
5 — FA50 (Terminal Output)
6 — FA51 (Analog Output Data from Comm. [FM])
7 — FA52 (Analog Output Data from Comm. [AM])
8 — F601 (Stall Prevention Level, %)
9 — F441 (Power Running Torque Limit 1 Level, 0.01%)
10 — F443 (Regen. Braking Torque Limit 1 Level, 0.01%)
11 — F460 (Speed Loop Proportional Gain)
12 — F461 (Speed Loop Stabilization Coefficient)
Direct Access Number — F831
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 3
Program Communications Communication Settings
Same as F831. See F831 for information on this parameter
Direct Access Number — F832
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 4
Program Communications Communication Settings
Same as F831. See F831 for information on this parameter
Direct Access Number — F833
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 5
Program Communications Communication Settings
Same as F831. See F831 for information on this parameter
Direct Access Number — F834
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 6
Program Communications Communication Settings
Same as F831. See F831 for information on this parameter
Direct Access Number — F835
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 7
Program Communications Communication Settings
Same as F831. See F831 for information on this parameter
Direct Access Number — F836
Parameter Type — Selection List
Factory Default — 0000h
Changeable During Run — Yes
F831 F836