Toshiba H9 Network Card User Manual


 
H9 ASD Installation and Operation Manual 231
Monitor Output Function Command 31
Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter
F969 selection to be recorded and output as a monitored function.
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.
Settings:
0 — Normal
1 — Peak
2 — Minimum
Direct Access Number — F970
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
Monitor Output Function 41
Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by
establishing the function that is to be recorded and output as the Peak,
Minimum, or Average value as selected at parameter
F971.
Select the Monitor Display Input Setting number from Table 10 on pg. 243 to
output the corresponding function.
Use the Communication Number if operating using communications.
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.
Direct Access Number — F971
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
Monitor Output Function Command 41
Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter
F971 selection to be recorded and output as a monitored function.
Settings:
0 — Normal
1 — Peak
2 — Minimum
See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.
Direct Access Number — F972
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
F970 F971