Toshiba H9 Network Card User Manual


 
H9 ASD Installation and Operation Manual 89
Input Terminal 4 (RES) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the RES discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable RES terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236.
Direct Access Number — F114
Parameter Type — Selection List
Factory Default — Reset Reset
Changeable During Run — No
Input Terminal 5 (S1) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S1 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S1 terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236.
Direct Access Number — F115
Parameter Type — Selection List
Factory Default — Preset Speed 1
Changeable During Run — No
Input Terminal 6 (S2) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S2 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S2 terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236.
Direct Access Number — F116
Parameter Type — Selection List
Factory Default — Preset Speed 2
Changeable During Run — No
Input Terminal 7 (S3) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S3 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S3 terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236.
Direct Access Number — F117
Parameter Type — Selection List
Factory Default — Preset Speed 3
Changeable During Run — No
Input Terminal 8 (S4) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S4 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S4 terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236.
Direct Access Number — F118
Parameter Type — Selection List
Factory Default — Preset Speed 4
Changeable During Run — No
F114 F118