H9 ASD Installation and Operation Manual 201
Panel Stop Pattern
Program ⇒ Special ⇒ Operation Panel Parameters
While operating in the Local mode this parameter determines the method used
to stop the motor when the stop command is issued via the EOI.
The Decel Stop setting enables the Dynamic Braking system that is setup at
F304 or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Deceleration Stop
1 — Coast Stop
Note: The Stop Pattern setting has no effect on the Emergency Off
settings of
F603. This parameter may also be accessed by
pressing the ESC key from the Frequency Command screen.
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
Panel Torque Command
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter sets the torque
command.
Direct Access Number — F725
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Panel Tension Torque Bias
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter sets the Torque
Bias.
Direct Access Number — F727
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Panel Load Sharing Gain
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter is used to set
the Load Sharing Gain.
Direct Access Number — F728
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Panel Override Multiplication Gain
Program ⇒ Special ⇒ Operation Panel Parameters
While operating using the LED Keypad Option this parameter provides a
value to be used in the event that
F729 (setting) is selected for the Frequency
Override Multiplying Input (F661).
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Units — %
F721 F729