H9 ASD Installation and Operation Manual 159
Regenerative Braking Torque Limit 3 Level
Program Torque Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F447
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 4 Level
Program Torque Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F448
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 4 Level
Program Torque Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F449
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Accel/Decel Operation After Torque Limit
Program Torque Torque Limit Settings
In a Crane/Hoist application that is operating using a mechanical brake, this
parameter is used to minimize the delay between the brake release and the
output torque reaching a level that can sustain the load.
This setting may reference time or the operating speed of the motor.
Settings:
0 — In Sync with Accel/Decel
1 — In Sync with Minimum Time
Direct Access Number — F451
Parameter Type — Selection List
Factory Default — In Sync with Accel/
Decel
Changeable During Run — Yes
Power Running Stall Continuous Trip Detection Time
Program Protection Stall
This parameter is used to extend the Overvoltage Stall (F305) and the
Overcurrent Stall (F017) time settings.
Direct Access Number — F452
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 1.0
Units — Seconds
F447 F452