Toshiba H9 Network Card User Manual


 
156 H9 ASD Installation and Operation Manual
Reverse Speed Limit Input
Program To r que Torque Control
This parameter Enables/Disables the Reverse Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the reverse
speed limit is controlled by the terminal selected here. If Setting is selected, the
value set at
F428 is used as the Reverse Speed Limit input.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Setting (F428)
Direct Access Number — F427
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Reverse Speed Limit Input Level
Program To r que Torque Control
This parameter provides a value to be used as the Reverse Speed Limit setting
if Setting is selected at
F427.
Direct Access Number — F428
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
Speed Limit (torque=0) Center Value Reference
Program To r que Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets the input terminal that will be used to control the allowable
speed variance.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — F431 Setting
Direct Access Number — F430
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Speed Limit (torque=0) Center Value
Program To r que Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets the targeted speed. The plus-or-minus value (range) for this
setting may be set at
F432.
Direct Access Number — F431
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F427 F431