Toshiba H9 Network Card User Manual


 
170 H9 ASD Installation and Operation Manual
Deceleration Time 4
Program Special Accel/Decel #1 – #4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The
Accel/Decel pattern may be set using
F502. The minimum Accel/Decel time
may be set using F508.
Note: A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
deceleration times.
Direct Access Number — F515
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Acceleration/Deceleration Pattern 4
Program Special Accel/Decel #1 – #4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #4 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F516
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Acceleration/Deceleration Switching Frequency 3
Program Special Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel #3 profile to the Accel #4 profile during a multiple-acceleration
profile configuration.
Direct Access Number — F517
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Pattern Operation Selection
Program Pattern Run Pattern Run
Pattern Run operation is enabled by selecting Seconds or Minutes as a unit of
measure for the Operation Time setting for the selected Preset Speeds.
See Parameter F523 for more information on Selections and Group Speeds
setup.
Settings:
0 — Disabled
1 — Enabled (units in seconds)
2 — Enabled (units in minutes)
Direct Access Number — F520
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Pattern Operation Mode
Program Pattern Run Pattern Run
This parameter sets the start condition of subsequent Pattern Runs after the
initial Pattern Run has been terminated or has completed its programming.
Settings:
0 — Reset After Stop
1 — Continue After Stop
Direct Access Number — F521
Parameter Type — Selection List
Factory Default — Reset After Stop
Changeable During Run — No
F515 F521