Toshiba H9 Network Card User Manual


 
200 H9 ASD Installation and Operation Manual
Display Bias
Program Utilities Display Parameters
In conjunction with the setting of F702, this parameter sets the bias of the front
panel speed display.
The frequency entered here will be multiplied by the setting of F702 and then
displayed as the zero value on the front panel display.
Direct Access Number — F706
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Change Step Selection 1
Program Utilities Display Parameters
In conjunction with the parameter setting of F708, this parameter sets the
amount that the output speed will increase or decrease for each speed command
change entered from the front panel using the Rotary Encoder.
Direct Access Number — F707
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Change Step Selection 2
Program Utilities Display Parameters
The parameter is used to modify the degree that the setting of F707 affects the
output speed changes that are input from the front panel using the Rotary
Encoder.
Selecting a zero value here disables this parameter and the resulting non-zero
value of parameter setting
F707 is output from the ASD.
Selecting a non-zero value here provides a dividend that will be used in the
following equation resulting in the actual output frequency applied to the motor.
Direct Access Number — F708
Parameter Type — Numerical
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Operation Command Clear Selection When ST Off
Program Special Operation Panel Parameters
Upon deactivation of the ST terminal while operating in the Local mode, the
motor will halt — this parameter setting is used to allow for the reactivation of
the motor without user intervention upon the reactivation of the ST terminal.
Upon reactivation of the ST terminal in this condition the ASD will resume the
Run condition and the motor will start (1 — Retain Run Command).
This feature may be Disabled and the Run command must be re-initiated by the
user for ASD operation (0 — Clear Panel Run Command).
WHEN ENABLED THE ASD WILL RESUME THE RUN CONDITION
WHEN THE ST TERMINAL IS REACTIVATED.
Settings:
0 — Clear Panel Run Command
1 — Retain Panel Run Command
Direct Access Number — F719
Parameter Type — Selection List
Factory Default — Retain Panel Run
Command
Changeable During Run — Yes
OutputFrequencyDisplayed InternallyCommandedFrequency
F708
F707
-------------
×=
DANGER
F706 F706