Toshiba H9 Network Card User Manual


 
248 H9 ASD Installation and Operation Manual
OC Over Current
ASD output current greater than
F601 setting.
Defective IGBT (U, V, or W).
ASD output to the motor is connected incorrectly.
Disconnect the motor and retry.
ASD output phase-to-phase short.
The ASD is starting into a spinning motor.
Motor/machine jammed.
Mechanical brake engaged while the ASD is starting or
while running.
Accel/Decel time is too short.
Voltage Boost setting is too high.
Load fluctuations.
ASD operating at an elevated temperature.
*OH Overheat
ASD ambient temperature
excessive.
ASD is operating at an elevated temperature.
ASD is too close to heat-generating equipment.
Cooling fan vent is obstructed (see Mounting the H9
ASD on pg. 15).
Cooling fan is inoperative.
Internal thermistor is disconnected.
OJ Timer Run-time counter exceeded. Type Reset required; select Clear run timer.
*OLI ASD Overload
Load requirement in excess of
the capability of the ASD.
The carrier frequency is too high.
An excessive load.
Acceleration time is too short.
DC damping rate is set too high.
The motor is starting into a spinning load after a
momentary power failure.
The ASD is improperly matched to the application.
OLM Motor Overload
Load requirement in excess of
the capability of the motor.
V/f parameter improperly set.
Motor is locked.
Continuous operation at low speed.
The load is in excess of what the motor can deliver.
*OLR Resistor
Overload
Excessive current at the
Dynamic Braking Resistor.
Deceleration time is too short.
DBR configuration improperly set.
LED
Display
LCD
Display
Description Possible Causes