158 H9 ASD Installation and Operation Manual
Regenerative Braking Torque Limit 1
Program ⇒ Torque ⇒ Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at F443 is used for this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 — F443 (setting)
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — F443 Setting
Changeable During Run — Yes
Regenerative Braking Torque Limit 1 Level
Program ⇒ To r que ⇒ Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque Limit
#1 if
F443 is selected at parameter F442.
Set this parameter to 250% to disable this function.
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Power Running Torque Limit 2 Level
Program ⇒ To r que ⇒ Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 2 Level
Program ⇒ To r que ⇒ Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F445
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 3 Level
Program ⇒ To r que ⇒ Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F446
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
F442 F446