266 H9 ASD Installation and Operation Manual
Note: (*) Indicates that the item is one of a set of two parallel cables.
Note: (**) Indicates that the item is one of a set of three parallel cables.
Table 21. 460-Volt H9 ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130H9U
MCP Rating
(Amps)
Wire/Cable Size Lug Size Range
Terminal
Board
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity
for Input/Output Power
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
Recommended Maximum 3Ø-Input 3Ø-Output
In-Lbs./Nm
4055 15 14 10
14 to 8
20
(3-core shield)
Torque to 5.3/0.6
11.5/1.3
4080 20 12 10
4110 30 10 8 12 to 8 17.7/2.0
4160 30 8 4
10 to 4
21/2.4
4220 50 8 4
4270 75 4 3
8 to 3
4330 75 6 3
4400 100 4 2
12 to 1/0 4 to 1/0 50/5.7 53/6.04500 100 3 2
4600 125 2 2
4750 175 1/0 4/0
6 to 250 1 to 300 275/31 168/19410K 200 2/0 4/0
412K 250 4/0 4/0
415K 300 *1/0 *4/0
6 to 250 275/31420K 400 *3/0 *250
425K 500 *250 *250
430K 600 *300 *350
4 to 350
375/42.4435K 700 *350 *350
440K 800 **250 **350 0 to 500 6 to 350