Power and Grounding
Figure 3-3 Mixed Grounding System
Table 3-1 Ground Point Descriptions for Mixed Grounding
Connection Description
Z1 48 VDC return.
Z2 Protective earth or safety ground (green/yellow).
Z3 Equipment ground for non isolated equipment.
Z4 Equipment ground for isolated equipment.
Z5 Equalizing frame ground. This ground creates low-impedance equalization
between frames.
B Battery ground.
1, 2, 3, 4 Connection points to the buildings ground system: a potential can exist between
these points within the ground system.
T Common-mode EMI filters.
Battery A
Non-isolated equipment
48V-A
T
48V-A
48V-A
logic power
+
48V-B
1
1
B
2
B
T
T
Safety Ground
Safety Ground
Safety Ground
48V-A RTN
48V-A
48V-A RTN
48V-B
48V-B RTN
48V-B
48V-B RTN
Safety Ground
Battery B
48V-B
+
Isolated equipment
48V-A logic power
48V-B
2
4
T
Z1
Z1
Z1
Z1
Z2
Z2
Z2
Z2
Z3
3
Z4
Z5
28311