MPCMM0001 Chassis Management Module Software Technical Product Specification 93
The Command Line Interface (CLI)
8.4.5.2 Target Dataitem Lists
When a target is specified, there is usually a slightly different set of dataitems specifically for that
target. Refer to Section 8.4.4, “Target Parameter: -t” on page 78 for more information on the target
parameter. Table 30 lists the possible dataitems used with various targets.
Table 29. Dataitem Keywords for FantrayN Location
dataitem Description
Get/
Set
CLI Get Output Valid Set Values
minorlevel
Used to set or query the
minorlevel for the fantray.
Both
Any value between
the normallevel and
the majorlevel of the
fantray.
normallevel
Used to set or query the
normallevel for the fantray.
Both
Any value between
the minimumsetting
and the minorlevel of
the fantray.
control
Used to set or query the control
mode of the fantray.
Both
EmergencyShutdown
fantray
CMM
defaultcontrol
defaultcontrol
Used to set or query the
defaultcontrol mode of the
fantray.
Both
fantray
CMM
restoredefaults
Used to restore the cooling table
defaults of the fan tray to the
vendor defaults or code defaults.
Set N/A true
minimumsetting
Used to query the minimum
setting of the fantray returned
via the getfantray properties
IPMI command.
Get N/A
maximumsetting
Used to query the maximum
setting of the fantray returned
via the getfantray properties
IPMI command.
Get N/A
recommendedsetting
Used to query the
recommended setting of the
fantray returned via the
getfantray properties IPMI
command.
Get N/A
currentfanlevel
Used to query the current
cooling level of the fantray.
Get
0
N/A