NOTE: In North America, AC power cords must not exceed 4.5 m (approximately
14.75 ft) in length, to comply with National Electrical Code (NEC) Sections 400-8
(NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3).
The cords supplied with the router are in compliance.
WARNING: The router is pluggable type A equipment installed in a restricted-access
location. It has a separate protective earthing terminal (sized for UNC 1/4-20 ground
lugs) provided on the chassis in addition to the grounding pin of the power supply
cord. This separate protective earthing terminal must be permanently connected to
earth.
CAUTION: Power cords and cables must not block access to router components or
drape where people could trip on them.
For information about the AC power supply, including a description of components,
see AC Power Supply on page 21. For instructions on connecting the power cord
and grounding cable during initial installation, see Connecting Power to an
AC-Powered Router on page 54. For instructions on replacing the AC power cord,
see Replacing an AC Power Cord on page 118.
Site Electrical Wiring Guidelines
When planning the electrical wiring at your site, consider the factors discussed in
the following sections.
Distance Limitations for Signaling
Improperly installed wires can emit radio interference. In addition, the potential for
damage from lightning strikes increases if wires exceed recommended distances, or
if wires pass between buildings. The electromagnetic pulse (EMP) caused by lightning
can damage unshielded conductors and destroy electronic devices. If your site has
previously experienced such problems, you might want to consult experts in electrical
surge suppression and shielding.
Radio Frequency Interference
You can reduce or eliminate the emission of radio frequency interference (RFI) from
your site wiring by using twisted-pair cable with a good distribution of grounding
conductors. If you must exceed the recommended distances, use a high-quality
twisted-pair cable with one ground conductor for each data signal when applicable.
Electromagnetic Compatibility
If your site is susceptible to problems with electromagnetic compatibility (EMC),
particularly from lightning or radio transmitters, you might want to seek expert
176 Site Electrical Wiring Guidelines
MX240 Ethernet Services Router Hardware Guide