5 - 17
5. PARAMETERS
Class No. Symbol Name and function
Initial
value
Unit
Setting
range
Control
mode
44 *DI3 Input signal selection 3 (CN1-3)
Allows any input signal to be assigned to CN1-pin 3.
The assignable signals and setting method are the same as in input
signal selection 2 (parameter No. 43).
Position
control mode
Input signals of
CN1-pin 3
selected.
Internal speed
control mode
0
0
This parameter is unavailable when parameter No. 42 is set to
assign the control change (LOP) to CN1-pin 3.
This parameter is unavailable when parameter No. 48 is set to
assign the Forward rotation stroke end (LSP) and Reverse rotation
stroke end (LSN) to be assigned to CN1-pin 3.
0882
Refer to
Name
and
function
column.
P S
45 *DI4
Input signal selection 4 (CN1-5)
Allows any input signal to be assigned to CN1-pin 5.
The assignable signals and setting method are the same as in input
signal selection 2 (parameter No. 43).
Position
control mode
Input signals of
CN1-pin 5
selected.
Internal speed
control mode
0
9
This parameter is unavailable when parameter No. 42 is set to
assign the control change (LOP) to CN1-pin 5.
This parameter is unavailable when parameter No. 48 is set to
assign the Forward rotation stroke end (LSP) and Reverse rotation
stroke end (LSN) to be assigned to CN1-pin 5
0995
Refer to
Name
and
function
column.
P S
Expansion parameters 1
46 *DI5
Input signal selection 5 (CN1-6)
Allows any input signal to be assigned to CN1-pin 6.
The assignable signals and setting method are the same as in input
signal selection 2 (parameter No. 43).
Position
control mode
Input signals of
CN1-pin 6
selected.
Internal speed
control mode
0
0
This parameter is unavailable when parameter No. 42 is set to
assign the control change (LOP) to CN1-pin 6.
This parameter is unavailable when parameter No. 48 is set to
assign the Reverse rotation stroke end (LSN) to be assigned to CN1-
pin 6.
0000
Refer to
Name
and
function
column.
P S