Deflecting the meter (analog indicator) to full-scale (1mA) at the
preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)
POINT
The calibration parameters "C1" can be made to be ready by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "FM terminal calibration".
(For details, refer to the instruction
manual (basic).)
MODE
4.
5.
Press the key to enable setting.
SET
SET
3.
SET
8.
SET
Flicker ... Parameter setting complete!!
SET
6.
RUN
PU
EXT
RUN
RUN
+
-
7.
1.
MODE
Pr. 30 must be set to "1".
2.
Turn the setting dial to show
" "
.
Operation
Display
In PU operation mode
Press the key to show
SET
" "
.
The parameter
number read
previously
appears.
By turning the
setting
dial , you can read another parameter.
SET
Press the key to return to the indication (step 3).
SET
Press the key twice to show the next parameter ( ).
Press the key to choose the
parameter setting mode.
Turn the
setting
dial until the
calibration parameter C1 "FM
terminal calibration" appears.
If the inverter is at a stop, press the
Press the key.
Setting is complete.
Turn the
setting
dial to
adjust the indicator needle
to the desired position.
Analog indicator
key to start it. (The motor
need not be connected.)