.4.2 Output frequency detection
The output frequency detection
signal (FU) is output when the
output frequency reaches or
exceeds the setting. This function
can be used for electromagnetic
brake operation, open signal, etc.
You can also set the detection of
the frequency used exclusively for
reverse rotation.
Forward
rotation
Reverse
rotation
Time
Output
signal
FU
Output
frequency (Hz)
Pr.42
Pr.43
ON
ON
OFF OFF OFF
This function is effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation (fall) during vertical
lift operation, etc.
Parameter Name
Factory
Setting
Setting
Range
Remarks
42
Output frequency
detection
6Hz 0 to 120Hz

43
Output frequency
detection for reverse
rotation
- - -
0 to 120Hz,
- - -
- - -: Same as
Pr. 42 setting
Setting is
enabled
when Pr. 30
= "1".
<Setting>
Refer to the above chart and set the corresponding parameters.
When Pr. 43 "output frequency detection for reverse rotation"
"- - -", the Pr.42
setting applies to forward rotation and the Pr.43 setting applies to reverse rotation.
Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used
for FU signal output.
CAUTION
Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions.
Make setting after confirming the function of each terminal.
Related parameters
Assignment of FU signal to terminal
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)
, Refer to , (page 62).
Refer to
(page 58).
Refer to (page 59).