Mitsubishi FR - S500 Power Supply User Manual


 
14
3) FR-S520S-0.1K to 1.5K (-R)
FR-S520S-0.2K to 1.5K-EC (R)
Cables (mm
2
)
(*2)
Motor
Output
(kW
(HP))
Inverter
Model
Rated current of
Circuit Breaker
(Refer to
page 15)
(*1)
Magnetic
Contactor
(MC)
(Refer to
page 17)
Power
Factor
Improving
AC Reactor
(Refer to
page 18)
(*3)
Power
Factor
Improving
DC Reactor
(Refer to
page 18)
(*3)
R, S
<L
1
, N>
U, V, W
0.1
(1/8)
FR-S520S-
0.1K
30AF/5A S-N10 FR-BAL-0.4K FR-BEL-0.4K 2 2
0.2
(1/4)
FR-S520S-
0.2K
30AF/10A S-N10 FR-BAL-0.4K FR-BEL-0.4K 2 2
0.4
(1/2)
FR-S520S-
0.4K
30AF/10A S-N20
FR-BAL-
0.75K
FR-BEL-
0.75K
22
0.75
(1)
FR-S520S-
0.75K
30AF/15A S-N20 FR-BAL-1.5K FR-BEL-1.5K 2 2
1.5
(2)
FR-S520S-
1.5K
30AF/20A S-N21 FR-BAL-2.2K FR-BEL-2.2K 2 2
4) FR-S510W-0.1K to 0.75K (-R)
FR-S510W-0.1K to 0.75K-NA
Cables (mm
2
)
(*2)
Motor
Output
(kW
(HP))
Inverter
Model
Rated current of
Circuit Breaker
(Refer to
page 15)
(*1)
Magnetic
Contactor
(MC)
(Refer to
page 17)
Power
Factor
Improving
AC Reactor
(Refer to
page 18)
(*3)
Power
Factor
Improving
DC Reactor
(Refer to
page 18)
(*4)
R, S
<L
1
, N>
U, V, W
0.1
(1/8)
FR-S510W-
0.1K
30AF/10A S-N10
FR-BAL-
0.75K
−−
−−−−
−−
22
0.2
(1/4)
FR-S510W-
0.2K
30AF/15A S-N10 FR-BAL-1.5K
−−
−−−−
−−
22
0.4
(1/2)
FR-S510W-
0.4K
30AF/20A S-N20 FR-BAL-2.2K
−−
−−−−
−−
22
0.75
(1)
FR-S510W-
0.75K
30AF/30A S-N20 FR-BAL-3.7K
−−
−−−−
−−
3.5 2
*1 For installations in the United States or Canada, the circuit breaker must be
inverse time or instantaneous trip type.
*2 The size of the cables assume that the wiring length is 20m (65.62feet).
*3 The power factor may be slightly less.
*4 The single-phase 100V power input model does not allow the power factor
improving DC reactor to be fitted.