Mitsubishi FR - S500 Power Supply User Manual


 
61
2
2
.3.4 Multi-speed operation
to
to
Used to switch between the predetermined running speeds.
Any speed can be selected by merely switching on/off the corresponding
contact signals (RH, RM, RL, REX signals).
By using these functions with Pr. 1 "maximum frequency" and Pr. 2 "minimum
frequency", up to 17 speeds can be set.
This function is valid in the external operation mode or in the combined
operation mode which is available when Pr. 79 = "3" or "4".
REX
Speed 1
(high speed)
Speed 5
Speed 6
Speed 7
Time
ON ON ONON
RM
ONONON
RL
RH
ON ON
ON
ON
Output frequency (Hz)
(low speed)
Speed 3
Speed 2
(middle speed)
Speed 4
Priority: RL>RM>RH
Time
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
ON ON ON ON
RH
ON ON ON ON
RM
ON ON ON ON
RL
ONON ON ON ON ON ON ON
REX
Output frequency (Hz)
Speed 8
Parameter Name
Factory
Setting
<EC version
>
Setting
Range
Remarks
4
Multi-speed setting
(high speed)
60Hz
<50Hz>
0 to 120Hz

5
Multi-speed setting
(middle speed)
30Hz 0 to 120Hz

6
Multi-speed setting
(low speed)
10Hz 0 to 120Hz

24 to 27
Multi-speed setting
(speeds 4 to 7)
- - -
0 to 120Hz,
- - -
"- - -" = no setting. Setting
enabled when Pr. 30 = "1".
80 to 87
Multi-speed setting
(speeds 8 to 15)
- - -
0 to 120Hz,
- - -
"- - -" = no setting. Setting
enabled when Pr. 30 = "1".
<Setting>
Set the running frequencies in the corresponding parameters.
Each speed (frequency) can be set as desired between 0 and 120Hz during inverter
operation.
When the parameter of any multi-speed setting is read, turn the setting dial
to
change the setting.
In this case, press the
SET
key (
WRITE
key) to store the frequency. (This is also
enabled in the external mode.)
The setting is reflected by pressing the
SET
key (
WRITE
key).
Assign the terminals used for signals RH, RM, RL and REX using Pr. 60 to Pr. 63.(*)