Mitsubishi FR - S500 Power Supply User Manual


 
80
2
.5 Current Detection Function Parameters
2
.5.1 Output current detection functions
If the output remains higher than the
Pr. 48 setting during inverter operation
for longer than the time set in Pr. 49,
the output current detection signal
(Y12) is output from the inverter's
open collector output terminal.
Output current
Time
Output current
detection
signal (Y12)
100ms
Pr.48
Pr.49
OFF OFFON
Parameter Name
Factory
Setting
Setting
Range
Remarks
48
Output current detection
level
150% 0 to 200%
49
Output current detection
signal delay time
0s 0 to 10s
Setting is enabled when
Pr. 30 = "1"
<Setting>
Parameter
Number
Description
48
Set the output current detection level.
100% is the rated inverter current.
49
Set the output current detection time. Set the time from when the output
current has risen above the Pr. 48 setting until the output current detection
signal (Y12) is output.
CAUTION
Once turned on because the current has risen above the preset detection level,
the output current detection signal is held on for at least 100ms (approximately).
Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other
functions. Make setting after confirming the function of each terminal.
Related parameters
Assignment of Y12 signal to terminal
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)