2
.3.15 Extended function display selection
Used to display the extended function parameters.
Refer to page 46 for the extended function parameter list.
Refer to the instruction manual (basic) for the parameter setting method.
Parameter Name
Factory
Setting
Setting
Range
Remarks
30
Extended function
display selection
00, 1
0: Without display,
1: With display
2
.3.16 Frequency jump to
When it is desired to avoid
resonance attributable to the
natural frequency of a mechanical
system, these parameters allow
resonant frequencies to be
jumped. Up to three areas may be
set, with the jump frequencies set
to either the top or bottom point of
each area.
Pr.33
Pr.34
2B
2A
Pr.36
Pr.35
Pr.32
Pr.31
Frequency jump
3B
3A
1B
1A
Running frequency (Hz)
The value set to 1A, 2A or 3A is a jump point and operation is performed at this
frequency.
Parameter Name
Factory
Setting
Setting Range Remarks
31 Frequency jump 1A - - - 0 to 120Hz, - - -
32 Frequency jump 1B - - - 0 to 120Hz, - - -
33 Frequency jump 2A - - - 0 to 120Hz, - - -
34 Frequency jump 2B - - - 0 to 120Hz, - - -
35 Frequency jump 3A - - - 0 to 120Hz, - - -
36 Frequency jump 3B - - - 0 to 120Hz, - - -
- - -: Function invalid
Setting is enabled when
Pr. 30 = "1"
<Setting>
To fix the frequency at 30Hz between Pr. 33 and Pr. 34
(30Hz and 35Hz), set 30Hz in Pr. 33 and 35Hz in Pr. 34.
Pr.34:35Hz
Pr.33:30Hz
To jump to 35Hz between 30 and 35Hz, set 35Hz in
Pr. 33 and 30Hz in Pr. 34.
Pr.33:35Hz
Pr.34:30Hz
CAUTION
During acceleration/deceleration, the running frequency within the set area is valid.
REMARKS
Write inhibit error " " occurs if the frequency jump setting ranges overlap.