Mitsubishi FR - S500 Power Supply User Manual


 
52
Func-
tion
Pa-
rame-
ter
Indica-
tion
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
84 *
Multi-speed
setting (speed
12)
0 to 120Hz, - - - 0.1Hz - - - 61
85 *
Multi-speed
setting (speed
13)
0 to 120Hz, - - - 0.1Hz - - - 61
86 *
Multi-speed
setting (speed
14)
0 to 120Hz, - - - 0.1Hz - - - 61
Multi-speed operation function
87 *
Multi-speed
setting (speed
15)
0 to 120Hz, - - - 0.1Hz - - - 61
88
PID action
selection
20: PID reverse action,
21: PID forward action
120101
89 *
PID
proportional
band
0.1 to 999%, - - - 0.1% 100% 101
90 *
PID integral
time
0.1 to 999s, - - - 0.1s 1s 101
91 PID upper limit 0 to 100%, - - - 0.1% - - - 101
92 PID lower limit 0 to 100%, - - - 0.1% - - - 101
93 *
PID action set
point for PU
operation
0 to 100% 0.01% 0% 101
PID control
94 *
PID differential
time
0.01 to 10s, - - - 0.01s - - - 101
95
Rated motor
slip
0 to 50%, - - - 0.01% - - - 109
96
Slip
compensation
time constant
0.01 to 10s 0.01s 0.5s 109
Slip compensation
97
Constant-
output region
slip
compensation
selection
0, - - - 1 - - - 109
98
Automatic
torque boost
selection
(Motor
capacity)
0.1 to 3.7kW, - - -
(0.2 to 3.7kW, - - - for
the 400V class.)
0.01kW - - - 109
Automatic torque
boost
99
Motor primary
resistance
0 to 50
, - - - 0.01
- - - 111
Pammeter List