Mitsubishi FR - S500 Power Supply User Manual


 
6
<When single-phase power input is provided for three-phase power input
inverter (NA version only)>
Reduce the output current.
FR-S520- K-NA inverter
0.1 0.2 0.4 0.75 1.5 2.2 3.7
Rated output current (A)
0.4 0.8 1.5 2.5 4.0 5.0 7.0
Power supply capacity (kVA)
0.4 0.8 1.5 2.5 4.5 5.5 9.0
AC input current (A)
1.1 2.4 4.5 6.4 11.2 12.9 17.4
Set m9 (Pr. 637) "current detection filter".
Setting "801" in the manufacturer setting parameter C8 enables you to set the m9
parameter.
CAUTION
Parameters other than m9 can also be made to be displayed, but never alter these
since they are manufacturer setting parameters.
m9 Setting Description
0 Single-phase power input
- - -
(Factory setting)
Three-phase power input
CAUTION
Always return the C8 parameter to 0 (factory setting) after you have finished the
setting of m9.