Mitsubishi FR - S500 Power Supply User Manual


 
164
4
(4) Single-phase 100V power supply
Japanese version
FR-S510W-0.1K to 0.75K (-R)
NA version
FR-S510W-0.1K to 0.75K-NA
Type FR-S510W- K(-R) 0.1 0.2 0.4 0.75
kW 0.1 0.2 0.4 0.75
Applicable motor capacity
(*1)
HP 1/8 1/4 1/2 1
Rated capacity (kVA) (*2) 0.3 0.5 1.0 1.6
Rated current (A) 0.8 1.4 2.5 4.1
Overload capacity (*3) 150% 60s 200% 0.5s (Inverse time characteristics)
Output
Voltage Three phase, 200V to 230V 50Hz/60Hz (*4, 6)
Rated input AC (DC) voltage,
frequency
Single-phase, 100V to 115V 50Hz/60Hz
Permissible AC (DC) voltage
fluctuation
90 to 132V 50Hz/60Hz
Permissible frequency
fluctuation
±
5%
Power supply
Power supply system
capacity (kVA) (*5)
0.5 0.9 1.5 2.5
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Self-cooling
Approximate weight (kg (lbs))
0.6
(1.32)
0.7
(1.54)
0.9
(1.98)
1.6
(3.52)
*1. The applicable motor capacity indicated is the maximum capacity applicable
when a Mitsubishi 4-pole standard motor is used.
*2. The rated output capacity indicated assumes that the output voltage is 230V.
*3. The % value of the overload capacity indicates the ratio of the overload current
to the inverter's rated output current.
For repeated duty, allow time for the inverter to return to or below the
temperatures under 100% load.
*4. For single-phase 100V power input, the output voltage provided cannot be
twice or more than the power supply voltage.
*5. The power supply capacity changes with the values of the power supply side
inverter impedances (including those of the input reactor and cables).
*6. For single-phase 100V power input, the application of motor load reduces the
output voltage about 10 to 15%. Therefore, the load must be reduced when a
general-purpose motor is used.