Mitsubishi FR - S500 Power Supply User Manual


 
114
Changing
example
Deflecting the meter (analog indicator) to full-scale (5V) at the
preset frequency of 60Hz (for frequency setting, refer to the
instruction manual (basic).)
POINT
The calibration parameters "C1" can be made to be ready by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "AM terminal calibration".
MODE
5.
6.
Press the key to enable setting.
SET
SET
RUN
PU
EXT
4.
SET
9.
SET
Flicker ... Parameter setting complete!!
SET
7.
RUN
PU
EXT
RUN
RUN
+
-
8.
2.
MODE
Pr. 30 must be set to "1".
3.
Turn the setting dial to show
" "
.
Operation
Display
1.
Confirm the RUN indication and operation
mode indication.
The inverter must be at a stop.
Press the key to show
SET
" "
.
The parameter
number read
previously
appears.
By turning the
setting
dial , you can read another parameter.
SET
Press the key to return to the indication (step 4).
SET
Press the key twice to show the next parameter ( ).
Press the key to choose the
parameter setting mode.
Turn the
setting
dial until the
calibration parameter C1 "AM
terminal calibration" appears.
Press the key to start the
inverter. (The motor need not be
connected.)
Press the key.
Setting is complete.
Turn the
setting
dial to
adjust the indicator needle
to the desired position.
(For details, refer to the instruction
manual (basic)).
Analog indicator
REMARKS
Depending on the set value, it may take some for the needle to move.
If "1" is set in Pr. 30 "extended function display selection", the calibration parameter
C1 "AM terminal calibration" can also be set in the external operation mode.
When the FR-PU04 is used, make calibration with Pr. 901.