Mitsubishi FR - S500 Power Supply User Manual


 
88
CAUTION
The frequency can be varied by RH (acceleration) and RM (deceleration)
between 0 and the maximum frequency (Pr. 1 setting).
When the acceleration or deceleration signal switches on, the set frequency
varies according to the slope set in Pr. 44 "second acceleration/deceleration time"
or Pr. 45 "second deceleration time". The output frequency acceleration and
deceleration times are as set in Pr. 7 "acceleration time" and Pr. 8 "deceleration
time", respectively. Therefore, the longer preset times are used to vary the actual
output frequency.
If the start signal (STF or STR) is off, turning on the acceleration (RH) or
deceleration (RM) signal varies the preset frequency.
CAUTION
When selecting this function, re-set the maximum frequency according to the
machine.
Related parameters
Maximum frequency setting
Pr. 1 "maximum frequency" (refer to page 59)
Output frequency acceleration/deceleration time
Pr. 7 "acceleration time",
Pr. 8 "deceleration time" (refer to page 62)
Time setting for acceleration/deceleration
Pr. 44 "second acceleration/deceleration time",
Pr. 45 "second deceleration time"
(refer to page 62)
2
.9 Terminal Function Selection Parameters
2
.9.1 Input terminal function selection
Use these parameters to select/change the input terminal functions.
Parameter Name
Factory
Setting
Setting
Range
Remarks
60
RL terminal
function
selection
0
61
RM terminal
function
selection
1
62
RH terminal
function
selection
2
0 to 10,
14, 16
63
STR terminal
function
selection
- - -
0 to 10,
14, 16,
- - -
Setting is enabled when Pr. 30 = "1"