Mitsubishi Electronics Q64TCTTBWN Network Card User Manual


 
116
(25)CH Control response parameter (Un\G49, Un\G81, Un\G113, Un\G145)
In the simple two-degree-of-freedom PID control, select the response speed to the change of the set value (SV)
from the following three levels: Slow, Normal, and Fast.
For details on the simple two-degree-of-freedom, refer to the following.
Page 188, Section 4.7
(a) Setting range
(b) Default value
The default values are set to Slow (0) in all channels.
Set value
Setting
contents
Description
0Slow
Set Slow when reducing an overshoot and undershoot to the change of the set value (SV).
However, the settling time is the longest of the three settings.
1 Normal Normal has features between Slow and Fast.
2Fast
Set Fast when speeding up the response to the change of the set value (SV). However, an
overshoot and undershoot is the largest of the three settings.
Common
Time
Temperature process value (PV)
Set value (SV) 2
Set value (SV) 1
Change
Set value (SV) change point
Fast
Normal
Slow