3.3.3 Details of output signals
(1) Setting/operation mode instruction (Yn1)
Use this signal to select the setting mode or the operation mode.
OFF: Setting mode
ON: Operation mode
Some buffer memory areas can be set only in the setting mode.
(a) Buffer memory areas that can be set only in the setting mode
The following settings can be changed only when Setting/operation mode instruction (Yn1) is off. If the settings
are changed in the operation mode, a write data error (error code:  3
H
) occurs.
Buffer memory area name
Buffer memory address
Reference
CH1 CH2 CH3 CH4
CH Input range Un\G32 Un\G64 Un\G96 Un\G128 Page 96, Section 3.4.2 (12)
Resolution of the manipulated value for
output with another analog module
Un\G181 Page 134, Section 3.4.2 (48)
CH Alert 1 mode setting Un\G192 Un\G208 Un\G224 Un\G240
Page 137, Section 3.4.2 (52)
CH Alert 2 mode setting Un\G193 Un\G209 Un\G225 Un\G241
CH Alert 3 mode setting Un\G194 Un\G210 Un\G226 Un\G242
CH Alert 4 mode setting Un\G195 Un\G211 Un\G227 Un\G243
CT CT selection Un\G272 to Un\G279 (set for each current sensor (CT)) Page 140, Section 3.4.2 (55)
CH Sensor two-point correction offset
value (measured value)
Un\G544 Un\G576 Un\G608 Un\G640 Page 142, Section 3.4.2 (58)
CH Sensor two-point correction offset
value (corrected value)
Un\G545 Un\G577 Un\G609 Un\G641 Page 142, Section 3.4.2 (59)
CH Sensor two-point correction gain
value (measured value)
Un\G546 Un\G578 Un\G610 Un\G642 Page 143, Section 3.4.2 (60)
CH Sensor two-point correction gain
value (corrected value)
Un\G547 Un\G579 Un\G611 Un\G643 Page 143, Section 3.4.2 (61)
CH Sensor two-point correction offset
latch request
Un\G548 Un\G580 Un\G612 Un\G644 Page 144, Section 3.4.2 (62)
CH Sensor two-point correction gain
latch request
Un\G550 Un\G582 Un\G614 Un\G646 Page 144, Section 3.4.2 (64)
CH Number of moving averaging Un\G698 Un\G699 Un\G700 Un\G701 Page 151, Section 3.4.2 (72)
Cooling method setting Un\G719 Page 151, Section 3.4.2 (73)
CH Process value (PV) scaling function
enable/disable setting
Un\G725 Un\G741 Un\G757 Un\G773 Page 152, Section 3.4.2 (76)
CH Process value (PV) scaling lower
limit value
Un\G726 Un\G742 Un\G758 Un\G774
Page 153, Section 3.4.2 (77)
CH Process value (PV) scaling upper
limit value
Un\G727 Un\G743 Un\G759 Un\G775
CH Derivative action selection Un\G729 Un\G745 Un\G761 Un\G777 Page 153, Section 3.4.2 (79)
CH Simultaneous temperature rise
group setting
Un\G730 Un\G746 Un\G762 Un\G778 Page 154, Section 3.4.2 (80)
CH Setting change rate limiter unit time
setting
Un\G735 Un\G751 Un\G767 Un\G783 Page 157, Section 3.4.2 (85)
Peak current suppression control group
setting
Un\G784 Page 158, Section 3.4.2 (86)
Sensor correction function selection Un\G785 Page 159, Section 3.4.2 (87)