347
CHAPTER 7 PROGRAMMING
7
7.3 When Using the Module on the Remote I/O Net
4. Display the refresh parameter setting window and configure the setting as follows.
Project window [Parameter] [Network Parameter]
[Ethernet/CC IE/MELSECNET]
5. Write the set parameter to the CPU module on the master station. Then reset the CPU module or
turn off and on the power supply of the programmable controller.
[Online] [Write to PLC...]
(7) Program example of when using the parameter of an intelligent function
module
(a) Setting on remote I/O station side
1. Create a project on GX Works2.
Select "QCPU (Q mode)" for "PLC Series:" and select "QJ72LP25/QJ72BR15(RemoteI/O)" for "PLC
Type:".
[Project] [New...]
or Power OFF ON
RESET