Mitsubishi Electronics Q64TCTTBWN Network Card User Manual


 
387
APPENDICES
A
Appendix 4 Online Module Change Procedure (When Using GX Developer)
Appendix 4.2 Conditions for online module change
Appendix 4.2 Conditions for online module change
To perform an online module change, a CPU module, a MELSECNET/H remote I/O module, the Q64TCN, GX
Developer, and a base unit as listed below are required.
Remark
The Q64TCN with the function version C supports the online module change since it was first released.
(1) CPU module
A Process CPU or Redundant CPU is required.
For the precautions on the multiple CPU system configuration, refer to the following.
QCPU User's Manual (Multiple CPU System)
For the precautions on the redundant system configuration, refer to the following.
QnPRHCPU User's Manual (Redundant System)
(2) MELSECNET/H remote I/O module
A module with function version D or later is required.
(3) GX Developer
GX Developer version 7.10L or later is required.
To perform an online change on a remote I/O station, GX Developer version 8.17T or later is required.
(4) Base unit
When a slim type main base unit (Q3SB) is used, an online module change cannot be performed.
When an extension base unit (Q5B) that does not require the power supply module is used, an online
module change cannot be performed for modules on all the base units connected.
(5) Buffer memory areas that can be saved and restored
The following table lists the buffer memory areas that can be saved and restored.
Buffer memory area name
Buffer memory address
Reference
CH1 CH2 CH3 CH4
CH Input range Un\G32 Un\G64 Un\G96 Un\G128 Page 96, Section 3.4.2 (12)
CH Stop mode setting Un\G33 Un\G65 Un\G97 Un\G129 Page 103, Section 3.4.2 (13)
CH Set value (SV) setting Un\G34 Un\G66 Un\G98 Un\G130 Page 104, Section 3.4.2 (14)
CH Proportional band (P) setting Un\G35 Un\G67 Un\G99 Un\G131 Page 105, Section 3.4.2 (15)
CH Integral time (I) setting Un\G36 Un\G68 Un\G100 Un\G132 Page 107, Section 3.4.2 (16)
CH Derivative time (D) setting Un\G37 Un\G69 Un\G101 Un\G133 Page 107, Section 3.4.2 (17)
CH Alert set value 1 Un\G38 Un\G70 Un\G102 Un\G134
Page 108, Section 3.4.2 (18)
CH Alert set value 2 Un\G39 Un\G71 Un\G103 Un\G135
CH Alert set value 3 Un\G40 Un\G72 Un\G104 Un\G136
CH Alert set value 4 Un\G41 Un\G73 Un\G105 Un\G137
CH Upper limit output limiter Un\G42 Un\G74 Un\G106 Un\G138
Page 110, Section 3.4.2 (19)
CH Lower limit output limiter Un\G43 Un\G75 Un\G107 Un\G139
CH Output variation limiter setting Un\G44 Un\G76 Un\G108 Un\G140 Page 112, Section 3.4.2 (20)